OPTIDRIVE HVAC

Input Ratings Supply Voltage 230V: 200 – 240V ± 10%
400V: 380 – 480V ± 10%
Supply Frequency 48 – 62Hz
Phase Imbalance 3% maximum
Inrush Current < rated current
Power Cycles 120/hour max, evenly spaced
Output Ratings Output Power 230V 1 Phase Input: 0.75 – 2.2kW
230V 3 Phase Input: 0.75 – 90kW
400V 3 Phase Input: 0.75 – 160kW
Overload Capacity 110% for 60 secs; 125% for 2 secs
Output Frequency Up to 120Hz
Ambient Conditions Temperature Storage: ¯40 to 60°C Operating: ¯10 to 40°C at default switching frequency (50°C max possible with derating)
Altitude 2000m max UL Approved 4000m max without UL Approval Up to 1000m with no derating (derate 1% /100m above 1000m)
Humidity 95% max, non-condensing
Enclosure Ingress protection IP55 standard
Programming Keypad Yes
PC Yes
Preset speeds 8 user adjustable
PID control Internal
Spin start Yes
Acceleration 0 – 3000 secs, 0.1 resolution
Deceleration 0 – 3000 secs, 0.1 resolution
Control Specification Control method V/F Voltage Vector Energy Optimiser V/F
Stopping mode Coast Stop Ramp to Stop DC Injection
Skip frequency Single point, user adjustable
0 – 10V
¯10 – 10V
0 – 20mA
Setpoint control 20 – 0mA 4 – 20mA
(internal) 20 – 4mA Master / Slave (Optibus) Modbus RTU
BACnet
Setpoint control (optional) Modbus TCP BACnet/IP
I/O Specification Digital inputs 10 – 30V DC, internal or external supply, NPN Response time < 4ms
Power supply 24V DC, 100mA, Short Circuit protected 10V DC, 5mA for Potentiometer
¯10 – 10V DC
Analog inputs 0 / 4 – 20mA 0 / 24V, 30V DC max Resolution: 12 bits + sign Response time < 4ms Accuracy: Better than 1% of full scale Parameter adjustable Scaling and Offset
Analog outputs 0 – 10V 0 / 4 – 20mA
Relay outputs Maximum Voltage : 250V AC, 30V DC Switching Current : 6A AC, 5A DC